The PHD Powerhouse AEC ST3060i-L Double Conversion Pure Sine Wave UPS w/ USB - 6kVA, LCD is part of a huge range of On-Line Double Conversion models which are completely digitally controlled. This UPS is suitable to protect different kinds of loads, from servers to computer networks, from medical instruments to security and surveillance systems. Capable of charging up to 100 A/H batteries, due to a stronger, built-in charger.
Cold Start | Yes, Default Frequency = 50Hz Or Settable |
Phase | Single Phase In, Single Phase Out |
Transfer Voltage Range | |
Line Low Transfer | 110VAC / 1165VAC / 120VAC |
Line Low Recovery | 116VAC / 122VAC / 127VAC |
Line High Transfer | 275VAC / 288VAC / 300VAC |
Line High Recovery | 268VAC / 279VAC / 291VAC |
Input Power Factor | ≥ 0.99 |
Input Frequency Range | 40Hz - 70Hz |
Generator | Supports Any Generator |
Output Power | 6kVA Max |
Output Power | 5.4kW Max |
Output Voltage | |
Waveform | Pure Sine Wave |
Nominal Voltage | 220 / 230 / 240VAC |
Voltage Regulation | ± 1% |
Transient Response | ≤5% (50% - 100% - 50%) |
Transient Recovery | ≤15ms (0% - 100% - 0%) |
Voltage Distortion | ≤5% THD, Non-Linear Load |
Output Frequency | |
Synchronization Range | Settable, ±3Hz Default |
Slew Rate | 0.5-5Hz/s , 2Hz Default |
Battery Mode | (50±0.05) Hz |
Transfer Time | |
Line Mode To Battery Mode | 0 |
Inverter To Bypass | 4ms |
Efficiency | |
Line Mode With Battery Full | 93% |
ECO Mode | 98% |
Battery Mode | 92% |
Battery Rating/Type | Depend On The Capacity Of External Batteries |
DC Voltage | 192/240VDC |
Battery-Low Voltage | (176±3)VDC |
Charger | |
Charging Voltage | (220±1%)VDC |
Charging Current (Max) | 5A |
Leakage Current | <1mA |
Width x Depth x Height | 250 x 504 x 480 mm |
Net Weight | 18Kg |
Free Shipping | No |
---|