The PHD Powerhouse ST2010 Line Interactive Pure Sinewave UPS - 1KVA, LCD Display With USB has a long standby option with no built-in batteries, this is the charge current of the long standby models. For long standby models, add "-L" to the part number.
Launched in 2005, the T2 Series benefits from the latest microprocessor Control Unit (MCU) technology, and now offers even greater value for money. The T2 is aimed at users that require protection from line voltage fluctuations and require a reliable and constant power source. The T2 is a sophisticated unit utilizing full digital control technology. Available with a power rating of 1kVA, 2kVA and 3kVA each with LCD display and audible alarm keeping you quickly updated on mains and battery status. The T2 is also fitted with an intelligent test button enabling a self-test routine which also prevents the UPS from being inadvertently switched off.
Fitted with an RS232 interface and USB port, which when used with the supplied software allows UPS status monitoring via the connected PC. Support for an optional SNMP network adapter is also provided enabling full network management functions. Under mains failure the T2 provides sinewave computer-grade power and will start a controlled shutdown (when software installed) of your operating system and connected hardware, completely protecting your data and working documents.
The UPS management software is installed on a server or workstation connected to each UPS via the serial or optional USB port. Power failure, power restoration, battery failure or eight events will be detected and the user informed. A shutdown will be initiated when the batteries are near to exhaustion or a technical problem occurs with the UPS. The UPS management software disconnects network connections, logs out users and closes open applications (subject to application/operating system support) before shutting down the operating system itself. A cost-effective solution to your power problems - the one you can afford.
Capacity Maximum | 1000VA/700W |
Input Voltage Range | 220/230/240VAC 25% Single Phase w/ Ground Input |
Input Frequency | 44Hz 56Hz |
Output Voltage | 220/230/240 VAC nominal |
Output Voltage Regulation | +- 2% ( Battery mode) |
Output Frequency | 46-54Hz (Normal mode), 50 0.1Hz ( Battery mode) |
Output THD | < 3% (line load) |
Efficiency(Battery mode) | >82% |
Overload Capability (Normal mode) | Sustaining 5 min, 100 - 200%; 3 sec @ > 200% |
Overload/Capability (Battery mode) | Sustaining 30 sec @ >100%; 1 sec @150% |
Battery Type | Sealed lead-acid maintenance-free 12VDC/ 7Ah per cell |
Numbers of Batteries | 2 cells |
Backup Time (at Full Load) | 11 min |
Battery Recharge Timeto 90% | < 8 hours (adjustable) |
Indication LCD | AC mode, Battery Mode, Output status, Battery Capacity, Overload, UPS Fault |
Battery Mode Alarm | Long beeping |
Audible Alarm Low Battery | Continuous beeping |
Overload Alarm | Short beeping |
Dimensions W x H x D (mm) | 150 x 220 x 460 |
Weight Net Weight w/Battery (kgs) | 19 |
Operating Temperature | -5-40 C |
Relative Humidity | < 95% (Non-Condensing) Environmental |
Audible Noise | < 45dBA @ 1 Meter |
CommunicationPort | Standard RS232 USB or SNMP/HTTP (optional) |
Free Shipping | No |
---|